Logo TEMCO Engineering, Inc. Made in the USA

Consistency Experts for the Pulp & Paper industry since 1985!

 

 

 
Technical Specifications

MAGIC III   SMART + HART
 

Power Requirements 2-wire, 24-29 volts DC, minimum 250 ohm loop
resistance. Motor 3 phase 440-480 VAC @ 60 Hz
Optional 110VAC Single Phase @60Hz available
Output Signal  4-20 mA (limited to 23 mA) into 350 ohm max. load @ 24 volts,700 ohms @ 29 volts.
Output Dampening Digital 1.5 to 100 seconds( 5 sec. factory setting )
Output Jacks 4  to 20 ma. Equal Upper & Lower Range
Pulp Curves TEN Calibration curve, 1 to 7% installed in transmitter. Curves selection via HART.
Span (Min. 1% Max. 5% )
Sensitivity Better than +/- 0.025% as % consistency
Repeatability +/- 0.3 % full scale (constant operating conditions)
Operating Conditions Max. stock Temp. 140 °F - Ambient  Temp.140°F
  Max. Process Pressure @ 257°F
Materials Wetted Parts : 316 S/S - Housing : Aluminum
Seal Cooling

Self-Contained cooling using heat transfer fluid.
No external water required.

Consistency Range adjustments made in % consistency from any HART device such as a Rosemount 275/375 Communicator.

Consistency Sensing Standard Motor Driven Disc and Shaft to Generate Torque from Consistency changes.
Torque Sensing Non-Contact Inductive coupling with Stationery Pick-Up Coil; approximately .030 in Air Gap.
MAGIC III
    Upgrade    
Can be installed on any existing pneumatic or electronic BTG® transmitter.

 

Sensor Motor Standard 440 vac 3 phase 1/2 hp @ 1 amp. Optional 575 vac motors are available.

 

Temco Engineering

© TEMCO Engineering, Inc. 2004 - All rights reserved.